Original file line number Diff line number Diff line change
Expand Up @@ -923,19 +923,17 @@ async def async_update(self) -> None:
and not self._fan
and not wants_humidity
):
# SCS-only gateways (F450, F453, F453AV, F454, F459, H4684, MH200, MH200N, MH202 in the
# firmware oracle; F455 and MH201 by field reports) expand the dimensionless zone status
# request *#4*Z## into four bus queries, dimension 0, 12, 14 and 13 ($0499ZZ3000 / 12 /
# 0E / 0D in trace-corpus.tsv). Against a 99-zone central unit every query is answered
# (F454 + #0, issue_629 log: *#4*1##..*#4*15## complete in ~1.3 s each with all five
# frames); a standalone thermostat answers only some of them, and the command session
# then ends with a NACK after 1.5-2 s (MH202 ACKs). The 10 s socket hang of #674 was an
# F455, not in the oracle, on actuator-only channels (*#4*Z*19*0*0##) where nothing
# answered. MyHomeServer1 replies to *#4*Z## from its cache (#649); F460 and F461 expand
# it into one request ($00499013000) and answer it (#714): those three keep the poll.
# Where the SCS-only gateway also drops the general request *#4*0##, the zone asks for
# its temperature below (_polls_temperature); everywhere else it waits for the sweep
# replies or for the thermostat's own reports.
# SCS-only gateways without multi-session *#4*Z## verification (F450, F453, F453AV, F459,
# H4684, MH200, MH200N in the firmware oracle; F455 and MH201 by field reports) expand
# the dimensionless zone status request *#4*Z## into four bus queries, dimension 0, 12, 14 and
# 13 ($0499ZZ3000 / 12 / 0E / 0D in trace-corpus.tsv). The 10 s socket hang of #674 was an F455,
# not in the oracle, on actuator-only channels (*#4*Z*19*0*0##) where nothing answered. F454
# (up to 4 command sessions) answers *#4*Z## in ~1.3 s and MH202 in ~160-250 ms with all five
# frames on both central units (#629) and standalone thermostats (#866); MyHomeServer1 replies
# from its cache (#649); F460 and F461 expand it into one request ($00499013000) and answer it
# (#714): those five keep the poll. Where an SCS-only gateway also drops the general request
# *#4*0##, the zone asks for its temperature below (_polls_temperature); everywhere else it waits
# for the sweep replies or for the thermostat's own reports.
return
if self._poll_health.should_skip(time.time()):
LOGGER.debug("%s %s did not answer its last polls; not asking again yet", self._gateway_handler.log_id, self._display_name)
Expand Down Expand Up @@ -963,8 +961,8 @@ async def async_update(self) -> None:
# is the bus TX timeout of an unpopulated zone (the QEMU images have no thermostat
# wired; the live F461 NACKs the unpopulated zone 1 the same way after 2.07 s, rows
# 374-376), not a verdict on a populated one. Until a command-session capture of
# *#4*Z*0## on an SCS-only gateway (F454 / MH200) exists, the result is left uncounted
# rather than risk marking a healthy zone unresponsive on a NACK.
# *#4*Z*0## on a single-session SCS-only gateway (MH200 / H4684) exists, the result is
# left uncounted rather than risk marking a healthy zone unresponsive on a NACK.
await self._gateway_handler.send_status_request(OWNHeatingCommand.get_temperature(self._full_where))
if self._fan and self._season_has_fan_coil():
await self._gateway_handler.send_status_request(
Expand Down
25 changes: 14 additions & 11 deletions custom_components/myhome/gateway.py
Original file line number Diff line number Diff line change
Expand Up @@ -211,15 +211,16 @@ def command_session_default(model: str | None) -> int:
) # *#16*0*5## (sound-who16-source.tsv)
# Zones of these SCS-only gateways report nothing after the startup sweep, so each zone asks
# for its temperature (*#4*Z*0##, one bus query answered in ~120 ms on a populated zone): the
# models refusing *#4*0## whose *#4*Z## is expanded into four bus queries ($0499ZZ3000 / 12 /
# 0E / 0D in trace-corpus.tsv, ~1.3 s per zone when a central unit answers them all, a NACK
# after 1.5-2 s when a standalone thermostat answers only some), and the MH201, whose
# standalone thermostats stayed unknown after every restart (#185; its *#4*0## refusal is the
# issue_466 sweep trace, the MH201 is not in the oracle). F460, F461 and MyHomeServer1 refuse
# *#4*0## too but answer *#4*Z## themselves (F460 and F461 expand it into one request,
# $00499013000 in trace-corpus.tsv; MyHomeServer1 replies from its cache, #649), so their zones
# keep the zone status poll and are not listed here.
ZONE_TEMPERATURE_POLL = frozenset({"F450", "F454", "F459", "H4684", "MH200", "MH201", "MH202"})
# single-session or uncaptured models refusing *#4*0## whose *#4*Z## is expanded into four bus
# queries ($0499ZZ3000 / 12 / 0E / 0D in trace-corpus.tsv), and the MH201, whose standalone
# thermostats stayed unknown after every restart (#185; its *#4*0## refusal is the issue_466
# sweep trace, the MH201 is not in the oracle). F454, MH202, F460, F461 and MyHomeServer1 refuse
# *#4*0## too but answer *#4*Z## themselves (F454 supports up to 4 command sessions and answers
# all five frames in ~1.3 s on both central-unit #629 and standalone #866 plants; MH202 answers
# all five frames in ~160-250 ms, #866; F460 and F461 expand it into $00499013000 in trace-corpus.tsv;
# MyHomeServer1 replies from its cache, #649), so their zones keep the zone status poll and are not
# listed here.
ZONE_TEMPERATURE_POLL = frozenset({"F450", "F459", "H4684", "MH200", "MH201"})
# Zones behind an F422 bus interface (WHERE Z#4#II): zero of the twelve emulated gateways in
# own-firmware-oracle (findings/thermo-zone-requests.md) emit $06EC / $06E4 interface-routed SCS
# frames for WHO 4. Gateways either NACK/drop Z#4#II queries, truncate Z#4#II at # and cross-poll
Expand Down Expand Up @@ -507,6 +508,10 @@ def firmware(self) -> str | None:
@property
def supports_zone_status(self) -> bool:
"""Whether the gateway supports point-to-point zone status queries (*#4*Z##)."""
profile = getattr(getattr(self, "gateway", None), "profile", None)
supported = getattr(profile, "supports_heating_zone_status", None)
if isinstance(supported, bool):
return supported
# Check the configured model string, its alphanumeric form (so "BTicino H/L4684" matches
# "HL4684"), and the profile model _profile_for_model resolves it to (L4684, NT4684,
# H/L4684, HL4684, HC4684, and MyHOME_Suite catalogue codes such as 003598).
Expand All @@ -522,10 +527,8 @@ def supports_zone_status(self) -> bool:
"F450",
"F455",
"HL4684", # "BTicino H/L4684" resolves to no profile and "H4684" is not a substring of it
"F454",
"MH200",
"MH201",
"MH202",
"F452",
"F453",
"F458",
Expand Down
14 changes: 12 additions & 2 deletions custom_components/myhome/gateway_sessions.py
Original file line number Diff line number Diff line change
Expand Up @@ -1421,8 +1421,18 @@ async def sending_loop(self, worker_id: int) -> None:
else:
_resolve_written(task, written_at)
self.handler._record_tx(written_at, task["message"])
if collected and isinstance(collected, list):
for resp in collected:
responses_to_dispatch: Any = collected
if responses_to_dispatch is None and task["is_status_request"]:
# A standalone zone status request (*#4*Z##) that answers only some of
# bt_H4690's four bus queries ends with *#*0## on the command session;
# OWNd preserves the partial frames in OWNNackError.responses.
responses_to_dispatch = getattr(
getattr(_command_session, "last_error", None),
"responses",
None,
)
if responses_to_dispatch and isinstance(responses_to_dispatch, list):
for resp in responses_to_dispatch:
raw_resp = str(resp)
if self.bus_monitor.has_frame_since(
task_start, direction="rx", raw=raw_resp
Expand Down
2 changes: 1 addition & 1 deletion docs/configuration/climate.md
Original file line number Diff line number Diff line change
Expand Up @@ -70,7 +70,7 @@ MyHOME climate entities support standard Home Assistant climate controls:
* **Target Temperature**: Adjustable setpoint slider in 0.5 °C increments.
The slider shows the setpoint the thermostat regulates to (dimension 12, knob offset included) whenever the zone has reported it; the commanded setpoint (dimension 14) is only shown until then. On an F461 the two can differ (21.0 commanded, 23.5 in force on a live capture), and the attribute `local_target_temperature` carries the same value. When the zone leaves `off`, the value reported while it was off is taken as the protection setpoint (#383), so the commanded setpoint is shown until the zone reports dimension 12 again; after a `set_temperature` call the next report, dimension 12 or 14, is shown. The value restored after a restart of Home Assistant already carries the saved `local_offset`, so the first dimension 13 report does not add it again.
* **Current Temperature**: Real-time ambient reading reported by the probe.
On SCS-only gateways whose firmware drops the general request `*#4*0##` (F450, F454, F459, H4684, MH200, MH201, MH202), each local zone asks for its own temperature with `*#4*<WHERE>*0##` after the startup sweep, so a standalone thermostat is not `unknown` until it next reports (#185). F460, F461 and MyHomeServer1 drop `*#4*0##` as well but answer the zone status request `*#4*<WHERE>##` themselves (the F460 and F461 expand it into the four dimension requests, the MyHomeServer1 replies from its cache), so their local zones keep that poll. A zone behind an F422 bus interface (`WHERE = <zone>#4#<interface>`) is never polled unless the OWNd profile sets `supports_interface_zone_requests = True` (see below), so it shows its restored reading until it reports by itself. After a restart the last reading is shown with the attribute `current_temperature_restored: true` until the zone reports again.
On single-session or uncaptured SCS-only gateways whose firmware drops the general request `*#4*0##` (F450, F459, H4684, MH200, MH201), each local zone asks for its own temperature with `*#4*<WHERE>*0##` after the startup sweep, so a standalone thermostat is not `unknown` until it next reports (#185). F454, MH202, F460, F461 and MyHomeServer1 drop `*#4*0##` as well but answer the zone status request `*#4*<WHERE>##` themselves (the F454 supports up to 4 command sessions and answers in ~1.3 s on both central-unit #629 and standalone #866 plants, the MH202 answers in ~160-250 ms, #866, the F460 and F461 expand it into one request, and the MyHomeServer1 replies from its cache), so their local zones keep that poll. A zone behind an F422 bus interface (`WHERE = <zone>#4#<interface>`) is never polled unless the OWNd profile sets `supports_interface_zone_requests = True` (see below), so it shows its restored reading until it reports by itself. After a restart the last reading is shown with the attribute `current_temperature_restored: true` until the zone reports again.
* **Current Humidity**: Ambient relative humidity percentage for zones equipped with humidity sensors (e.g. Living Now thermostats or humidity probes).
* **HVAC Action and `actuators`**: a local zone asks for the state of its actuators (`*#4*<WHERE>*20##`, one `*#4*#0*20##` for every local zone on an F461 or a MyHomeServer1) once the startup sweep is over and again after the event session reconnects, so `hvac_action` (`heating` / `cooling` / `idle`) is known right after start instead of after the first actuator switch. The attribute `actuators` lists each actuator as `on` or `off` (`{"1": "off", "2": "off"}`) and stays while the zone is off (every actuator `off`). F453, F453AV, H4684, MH200, MH200N and MH202 drop the request (firmware oracle), so their zones are not asked and wait for the actuators' own frames; on a shared bus the gateway that serves WHO 4 (delegated secondary or warm standby) decides. Secondary probes (`WHERE >= 100`) are never asked. Probe-less `F430/2` / `F430/4` relays (such as bathroom towel warmers that only emit Dimension 20 actuator status frames without a temperature probe) do not create phantom `climate` entities and can be controlled as `switch` entities via **Add thermo actuator / towel-warmer switch (WHO 4)** (see [Switches & Relays](switches.md)).
* **Zones Behind an `#4#II` Interface (`F422`)**: across all twelve emulated gateway firmwares in `own-firmware-oracle` (`findings/thermo-zone-requests.md`), **zero** gateways emit `$06EC`/`$06E4` interface-routed SCS telegrams for `WHO = 4`: gateways either NACK/drop `#4#II` queries, truncate `Z#4#II` at `#` and cross-poll local zone `Z` on the main bus (`F450`, `F454`, `F459`, `F460`, `F461`, `H4684`, `MH200`, `MyHomeServer1`), or on `MH202` (`1.0.24`) misparse trailing `#4#01` as local zone 4 actuator 1 and crash `coso` (`SIGSEGV`) on `*#4*Z#4#01##`. Unless an `OWNd` gateway profile explicitly declares `supports_interface_zone_requests = True`, zones configured with an `#4#II` interface are passive: neither polls (`*#4*Z#4#II##`, `*0##`, `*11##`, `*19##`, `*20##`, `*60##`) nor writes that would strip `#4#II` onto local main-bus zone `Z` are sent, while incoming event-session broadcasts update state normally (note that 1-digit inline shorthand `3#4#1`..`3#4#9` is normalized as zone `3` behind interface `01`..`09`; wire frames always use two-digit `#4#01`..`#4#15`). Dimensionless and zone-dimension polls on actuator or split addresses (`Z#N`, `Z#0`, `0#N`, `3#Z#N`) are likewise never sent.
Expand Down
2 changes: 1 addition & 1 deletion docs/configuration/runtime_behaviour.md
Original file line number Diff line number Diff line change
Expand Up @@ -12,7 +12,7 @@ After the event session is up, the integration sends a small set of general stat
| :--- | :--- | :--- |
| `*#1*0##` | Lighting | All gateways |
| `*#2*0##` | Automation / covers | All gateways |
| `*#4*0##` | Thermoregulation | All gateways except F450, F454, F459, F460, F461, H4684, MH200, MH201, MH202 and MyHomeServer1, whose firmware drops it (firmware oracle; the MH201 from a physical sweep trace, `tests/fixtures/traces/issue_466`); F460, F461 and MyHomeServer1 poll `*#4*<WHERE>##` per zone instead, and the zones of the SCS-only models (F450, F454, F459, H4684, MH200, MH201, MH202) ask `*#4*<WHERE>*0##` |
| `*#4*0##` | Thermoregulation | All gateways except F450, F454, F459, F460, F461, H4684, MH200, MH201, MH202 and MyHomeServer1, whose firmware drops it (firmware oracle; the MH201 from a physical sweep trace, `tests/fixtures/traces/issue_466`); F454, MH202, F460, F461 and MyHomeServer1 poll `*#4*<WHERE>##` per zone instead (#629, #649, #714, #866), and the zones of the remaining SCS-only models (F450, F459, H4684, MH200, MH201) ask `*#4*<WHERE>*0##` |
| `*#5*0##` | Burglar alarm | MH202, H4890 |
| `*#16*0*5##` | Sound system (dimension 5; lists every amplifier) | Gateways whose profile advertises WHO 16, except F450, F459, F460, F461, MH202 and MyHomeServer1, whose firmware drops it (firmware oracle) |
| `*#18*51*51##` | Energy management (meter 51 total energy) | F454, F455, MH201, MH202, MyHomeServer1, H4890 |
Expand Down
4 changes: 2 additions & 2 deletions docs/getting-started/hardware-compatibility.md
Original file line number Diff line number Diff line change
Expand Up @@ -59,9 +59,9 @@ During startup initial discovery, status queries are gated by the gateway profil
<!-- GATEWAY_DISCOVERY_START -->
| Gateway Model | Profile Subsystems (advertised) | Startup Sweep Requests (sent) | Profile Support Notes |
| :--- | :--- | :--- | :--- |
| **MH202** | WHO 1, 2, 4, 5, 16, 18 | WHO 1, 2, 5, 18 (firmware drops `*#4*0##`, `*#16*0*5##`) | Burglar Alarm (`*#5*0##`) and Energy (`*#18*51*...`) queries. WHO 4 and WHO 16 are advertised, but the `010024` firmware drops `*#4*0##` and `*#16*0*5##` (own-firmware-oracle), so the sweep leaves both out and each climate zone asks `*#4*<WHERE>*0##` itself. |
| **MH202** | WHO 1, 2, 4, 5, 16, 18 | WHO 1, 2, 5, 18 (firmware drops `*#4*0##`, `*#16*0*5##`) | Burglar Alarm (`*#5*0##`) and Energy (`*#18*51*...`) queries. WHO 4 and WHO 16 are advertised, but the `010024` firmware drops `*#4*0##` and `*#16*0*5##` (own-firmware-oracle), so the sweep leaves both out; climate zones are polled with `*#4*<WHERE>##` (#866). |
| **H4890 / AM4890** | WHO 1, 2, 4, 5, 16, 18 | WHO 1, 2, 4, 5, 16, 18 | Supports Burglar Alarm, Sound (`*#16*0*5##`), and Energy meter 51 queries. |
| **F454** | WHO 1, 2, 4, 16, 18 | WHO 1, 2, 16, 18 (firmware drops `*#4*0##`) | Full lighting, cover, sound (`bt_difson` firmware-verified), and energy meter 51 queries. The `020051` firmware drops `*#4*0##` (own-firmware-oracle), so each climate zone asks `*#4*<WHERE>*0##` itself. Alarm query omitted. |
| **F454** | WHO 1, 2, 4, 16, 18 | WHO 1, 2, 16, 18 (firmware drops `*#4*0##`) | Full lighting, cover, sound (`bt_difson` firmware-verified), and energy meter 51 queries. The `020051` firmware drops `*#4*0##` (own-firmware-oracle), so the sweep leaves it out; zones are polled with `*#4*<WHERE>##` (#629, #866). Alarm query omitted. |
| **F452 / F453 / F453AV** | WHO 1, 2, 4, 16, 18 | WHO 1, 2, 4, 16, 18 | Lighting, cover, climate, sound (`bt_difson` firmware-verified on F453/F453AV), and energy meter 51 queries. Alarm query omitted. |
| **F461** | WHO 1, 2, 4, 18 | WHO 1, 2, 18 (firmware drops `*#4*0##`) | Lighting, cover, and energy meter 51 queries. Sound is WHO 22 only (no `bt_difson`; every WHO 16 frame refused, own-firmware-oracle `020011`, confirmed live on 2.0.11). The firmware also drops `*#4*0##`, so the sweep leaves it out; zones are polled with `*#4*<WHERE>##`. Alarm query omitted. |
| **F455** | WHO 1, 2, 4, 18 | WHO 1, 2, 4, 18 | Entry-level gateway: lighting, cover, climate, and energy meter 51 queries. Sound (WHO 16/22) and Alarm (WHO 5) omitted per installer manual. |
Expand Down
4 changes: 2 additions & 2 deletions scripts/update_gateway_profiles.py
Original file line number Diff line number Diff line change
Expand Up @@ -202,7 +202,7 @@
"profile_name": "MH202",
"pinned_whos": [1, 2, 4, 5, 16, 18],
"sweep_omits": [GENERAL_ZONE_STATUS, SOUND_STATUS],
"notes": "Burglar Alarm (`*#5*0##`) and Energy (`*#18*51*...`) queries. WHO 4 and WHO 16 are advertised, but the `010024` firmware drops `*#4*0##` and `*#16*0*5##` (own-firmware-oracle), so the sweep leaves both out and each climate zone asks `*#4*<WHERE>*0##` itself.",
"notes": "Burglar Alarm (`*#5*0##`) and Energy (`*#18*51*...`) queries. WHO 4 and WHO 16 are advertised, but the `010024` firmware drops `*#4*0##` and `*#16*0*5##` (own-firmware-oracle), so the sweep leaves both out; climate zones are polled with `*#4*<WHERE>##` (#866).",
},
{
"model": "**H4890 / AM4890**",
Expand All @@ -216,7 +216,7 @@
"profile_name": "F454",
"pinned_whos": [1, 2, 4, 16, 18],
"sweep_omits": [GENERAL_ZONE_STATUS],
"notes": "Full lighting, cover, sound (`bt_difson` firmware-verified), and energy meter 51 queries. The `020051` firmware drops `*#4*0##` (own-firmware-oracle), so each climate zone asks `*#4*<WHERE>*0##` itself. Alarm query omitted.",
"notes": "Full lighting, cover, sound (`bt_difson` firmware-verified), and energy meter 51 queries. The `020051` firmware drops `*#4*0##` (own-firmware-oracle), so the sweep leaves it out; zones are polled with `*#4*<WHERE>##` (#629, #866). Alarm query omitted.",
},
{
"model": "**F452 / F453 / F453AV**",
Expand Down